Model | Rated voltage ratio |
Rated current ratio |
frequency |
Voltage Transformer Accuracy
Class and Determined Output |
Current Transformer Accuracy Class
and Rated Output |
Rated insulation | Standard code | ||
0.2级 | 0.5级 | 0.2级 | 0.2级 | ||||||
JLS-3 JLS-6 JLS-10 | 3000/100 | 5-300/5 | 50 | 20 | 25 | 10 | 10 | 3.6/25/40 | GB1208-2006 GB1207-2006 GB17021-2006 |
6000/100 | 5-300/5 | 50 | 20 | 25 | 10 | 10 | 702/30/60 | ||
6300/110 | 5-300/5 | 50 | 20 | 25 | 10 | 10 | 702/30/60 | ||
10000/100 | 5-300/5 | 50 | 25 | 25 | 10 | 10 | 12/42/75 | ||
JLS-35 | 35000/100 | 5-300/5 | 50 | 25 | 20 | 10 | 10 | 40.5/95/185 |
The main purpose
It is suitable for three-phase AC lines with rated frequency of 50Hz and rated voltage of 6, 10, and 35kV. Outdoor direct measurement of active and non-condensing energy in the line
The main function
This product is mainly composed of a combined transformer and an electroplating meter box. The combined transformer is composed of two or three single-phase voltage transformers and current transformers, and 25# transformer oil is used as an insulation cut-off. The first and second occurrences are installed on the panel with a porcelain sleeve. The electroplating meter box is installed on the side of the combined transformer and consists of a constant active watt-hour meter and a reactive watt-hour meter. Kuyou has the advantages of high metering accuracy, light weight, easy installation, and anti-stealing lights.
Use environment
a. Ambient temperature: - 25- 40, the daily average does not exceed +30 ℃
b. The altitude of the installation site shall not exceed 1000m.
c. There is no serious pollution in the atmosphere, and there is no gas or conductive dust in the medium that is enough to corrode metals and destroy insulation.
d. The installation site is free from severe vibration and bumps, and the installation inclination is not more than 5°.
Parameter
Product performance conforms to: GB17201
Rated voltage: 6kV, 10kV, 35kV
Accuracy grades: 0 to 5 and 0.2, 0.5S and 0.2S
Rated voltage ratio: 6000/100V, 10000/100V, 35000/100V
Current ratio: 5-300/5A (large current ratio can be customized)